New Hybrid Controller Using Optimal Design of Coefficient Diagram Method (CDM) to Automatic Voltage Regulator (AVR) Through Turbulent Flow of Waterbased Optimization Algorithm
Received Date: November 05, 2024 Accepted Date: December 05, 2024 Published Date: December 08, 2024
doi: 10.17303/jdmt.2024.1.205
Citation: Due Mina Heshmati, Iraj Faraji, Saeid Jalilzadeh, Reza Noroozian, Hosein Shayeghi (2024) New Hybrid Controller Using Optimal Design of Coefficient Diagram Method (CDM) to Automatic Voltage Regulator (AVR) Through Turbulent Flow of Water-based Optimization Algorithm 1: 1-23
Abstract
Changes in the power demand, such as changes in consumption patterns during the COVID-19 era, have caused voltage fluctuations in the power system. One of the most straightforward approach to controlling such fluctuations is injecting reactive power via a synchronous generator. The excitation system utilizes an automatic voltage regulator (AVR) control loop to achieve reactive power control for the synchronous generator. The faster and more accurate this AVR control loop is, the faster the voltage fluctuations dampen. This paper utilizes a novel hybrid controller, incorporating the numerical method known as the coefficient diagram method (CDM) and optimization techniques based on laws, algebraic calculations, and constraints. Additionally, it incorporates the Turbulent Flow of a Water-based Optimization Algorithm (TFWO) and a robust hybrid objective function to effectively control the AVR system. In this control method, water flow turbulence algorithm is employed to adjust the parameters of the proposed control. To show the efficiency of the proposed control strategy, it has been tested and compared on a standard system. The proposed strategy outperforms other methods in terms of performance criteria measured in both the time and frequency domains. The figures and numerical results demonstrate this superiority. Furthermore, unlike other approaches, this strategy does not necessitate resetting the control parameters obtained at the operating point. The results also emphasize the high speed, stability, and robustness of the suggested method.
Keywords: Automatic voltage control (AVR), Coefficient diagram method (CDM), Turbulent Flow of Water-based Optimization Algorithm (TFWO), Coronavirus 2019 (COVID-19).
Graphical Abstract
Introduction
The new coronavirus (SARS-CoV2) was first detected in December 2019 in Wuhan, China. A new infectious disease called COVID-19 spread rapidly in China and then around the world [1]. The virus has been defined by the World Health Organization (WHO) as an epidemic and has affected most parts of Europe, the Americas, and Asia [2,3]. Ministry of Health Governments have declared red status and ordered home quarantine in some cities to reduce the incidence and mortality of COVID-19, and in some countries, even the commercial and industrial sectors were closed. This home quarantine trend has drastically reduced electricity demand and changed the pattern of load consumption and daily load characteristics. These abrupt changes in the consumption pattern, imposed on electricity companies and the distribution system due to special circumstances, have created a new challenge in supplying energy to consumers. This new challenge has caused voltage fluctuations, increased losses, and imbalances in the power system [4,5].
Shifting the electricity demand pattern has caused problems in voltage regulation in some areas of the power system [6]. Reducing the consumption of some consumers during the day and increasing the distributed generation (DG) sources’ penetration in the power system has led to an increase and fluctuation of voltage in the power system [4,7]. This is especially the case in some local areas with large numbers of factories and commercial buildings that have been completely or partially shut down during the outbreak of COVID-19. The alteration in real power demand impacts the frequency, whereas the modification in reactive power primarily influences the magnitude of voltage [5,6]. This increase in voltage fluctuations due to reduced load consumption and prolonged low power demand must be offset by some sources. Because voltage control in the power system is mostly realized by reactive power, some power sources must be exploited in the power system that can control voltage fluctuations. These techniques encompass the utilization of generators, static reactive power compensators (SVCs), flexible alternating current transmission system (FACTS) devices, capacitors, and reactors [8–10]. Reactive power control and reduction of generator terminal voltage fluctuations are carried out by controlling the reactive power of the generators and by regulating the excitation current and excitation field. To this end, the amount of reactive power injected into the power system and, finally, the voltage can be controlled using a generator’s excitation system. These methods involve employing generators, static reactive power compensators (SVCs), flexible alternating current transmission system (FACTS) devices, capacitors, and reactors [11,12]. The purpose of an automatic voltage regulator (AVR) is to maintain the voltage at the designated level at the synchronous generator terminal by injecting reactive power through the generator.
The automatic voltage regulator (AVR) control loop is considered one of the fundamental control loops within a power plant. Due to the fact that instability in the automatic voltage regulator (AVR) can result in instability of the entire power system, the performance of its control system is exceptionally sensitive [13]. This system receives its signals from different parts and generates the AVR control signal. This signal is to reduce the voltage error, and all limiters have acted on it, i.e., the control signal is calculated so that none of the limits are neglected [14].
In recent times, numerous controllers have been explored by researchers to address the issue of automatic voltage control in power systems and enhance the system's response. Among these controllers are proportional-integral-derivative (PID) controllers, fuzzy logic-based controllers, robust controllers, and controllers based on neural networks. These controllers are developed using nonlinear and robust techniques, as well as heuristic and metaheuristic intelligent algorithms.
In [15], the nonlinear and robust control method (H2/H∞) is used to design the AVR controller. The linear matrix inequality (LMI) technique has been used to solve the issue of constrained optimization and maintain system stability. In [16], the investigation focuses on the fractional- order (FO) proportionalintegral-derivative (PID) controller applied to the AVR system. The AVR system’s performance criteria are defined as perturbations within the system and subsequently optimized using the multiobjective differential evolution (MODE) optimization algorithm to achieve multiple objectives. The hybrid controller used is combined with the H2/H∞ method. In [17], H∞ robust control method μ-analysis are used to control AVR. This study considers the uncertainty associated with the system parameters. In [18], to strengthen the performance of the system controller against relatively severe disturbances caused by the load, a PI controller with state feedback with two degrees of freedom (2-DOF) is presented, in which the controller coefficients are adjusted by particle swarm optimization (PSO) algorithm. The researchers in reference [19] propose a controller called the interval type-2 fractional order fuzzy PID (IT2FO- FPID) controller. A novel approach is introduced, which combines a type 2 TakagiSugeno-Kang (TSK) fuzzy logic controller (IT2FLC) with a PID fractional-order controller. This combined controller aims to effectively handle uncertainties in the nonlinear operation of the system. In [20], to determine the optimal parameters of an AVR (Automatic Voltage Regulator) PID controller, a hybrid model is employed. This model integrates genetic algorithm (GA), radial basis function neural network (RBF-NN), and Sugeno fuzzy logic. In [21], the AVR generator controller utilizes a fractionalorder model reference adaptive controller (FOMRAC). The AVR generator controller utilizes a fractional-order model reference adaptive controller (FOMRAC). In [22], the AVR system integrates a fuzzy controller that automatically adjusts itself. To enhance performance, the scaling factors in this controller are optimized using the PSO algorithm. An online adaptive optimization controller is designed in [23] to optimize AVR performance. To solve the optimal control problem, quadratic optimization using the Adaptive Dynamic Programming (ADP) method is employed. Reference [24] utilizes a combination of a fuzzy controller PID and a programmable logic controller (PLC) to regulate the generator terminal voltage through the AVR system. In reference [25], an AVR system employs a fuzzy logicbased controller optimizing the Fuzzy P + Fuzzy I + Fuzzy D (FP + FI + FD) controller using a hybrid algorithm. The scaling factors of the fuzzy system control are determined using the hybrid GA- PSO (HGAPSO) algorithm. Reference
[26] implements a FOPIλDμ fractional-order controller for the AVR system. The fractional-order control parameters are adjusted by incorporating the improved chaotic genetics II algorithm. In [27], two controllers are exploited to automatically adjust the generator voltage simultaneously. These two controllers are designed based on fuzzy set and type 2 fuzzy logic combined with the PI controller. Ref. [28], uses a self-adjusting PID fuzzy controller for the AVR system and proper performance against uncertainty. Additionally, the TLBO optimization algorithm is applied to enhance the suggested control efficiency. Reference [29] employs a robust control design method to create a controller for the AVR + LFC (Automatic Voltage Regulator + Load Frequency Control) system. In this paper, the nonlinear threshold accepting (NLTA) method and nonlinear NP problem solution in a short time have been used to adjust the control parameters. Moreover, metaheuristic methods such as PSO [30], hybrid GA-bacterial foraging optimization (GA-BF) [31], Manta ray foraging optimization algorithm (MRF) [32], JAYA optimization algorithm [33], Cuckoo optimization algorithm (COA) [34], symbiotic organisms search algorithm (SOSA) [35], Whale Optimization Algorithm (WOA) [36], and Tree Seed Algorithm (TSA) [37] the design of optimal parameters for the PID controller in the synchronous generator's AVR system utilizes these approaches. Reference [34] proposes the utilization of a chaotic multi-objective method to design a fractional-order PID controller for the AVR system. This manuscript focuses on considering the linear model of the system. The fuzzy controller method optimized with the PSO algorithm is presented to improve the voltage stability in the generator excitation system in AVR [38].
The industrial sector has shown increased interest in classic controllers like PID, primarily because of their straightforward structure and convenient implementation. Because the adjustment of the PID and classical controller coefficients depends on the operating point of the system, and these controllers are usually adjusted in the same operating conditions. Furthermore, the power system poses challenges such as time delay, high order, the nonlinearity of system elements, parameter uncertainty, diverse operating conditions, unexpected power system disturbances, and uncertainties in modeling reactive power changes, as mentioned in reference [39]. Besides, by changing the system conditions, it is impossible to change the PID coefficients quickly and simultaneously, and the parameters of these controllers are obtained based on trial and error in nominal operating points and do not have a specific method with mathematical support. Although it is the simplest and cheapest control method available in the industry, it is not robust against the above conditions. Hence, in recent years, there has been a research emphasis on developing controllers that can deliver optimal performance for the power system amidst varying system parameters and machine conditions. Consequently, to tackle the challenges of robust design and performance in the face of uncertainties, novel control strategies have emerged. These strategies are built upon more advanced approaches such as adaptive control, robust control, predictive control, sliding mode control, and state feedback control, as well as incorporating fuzzy logic and neural networks. Some approaches even combine multiple methods to achieve better outcomes. Although these methods certainly provide better results than classical control, they have very complex processes and calculations and require comprehensive and accurate information from the control system, including information about all state variables; hence they have not become widely applicable in the industry. On the other hand, given the increasing complexity of power systems, restructuring, and economic concepts such as the electricity market, there is a need for novel, robust, yet achievable control strategies.
To address the issues outlined in this paper, a novel controller named CDM has been employed as a solution. This control strategy divides the previous methods into two categories, i.e., classical or modern, and by introducing a new method, it is in a third category called algebraic methods. Although this control strategy is new, it has been used in the industry for about 40 years to control servo motors, spacecraft, gas turbines, etc., and has been addressed in power engineering and control scientific papers for the last few years [40–44]. These papers indicate a better response to this controller than controllers such as predictive and classical controllers. This method offers several notable features and advantages. It utilizes algebraic polynomials to represent both the system and the controller, employs a control system structure with two degrees of freedom (2DOF), achieves a system step response without overshoot or with minimal overshoot, leverages robust mathematical principles for indirect pole placement in the closed-loop system, and enables a rapid settling time to attain the desired robust response. These characteristics contribute significantly to the effectiveness and benefits of this approach. Consequently, the controller designer can evaluate and estimate the speed, stability, and robustness of the controlled system. These three crucial performance indicators hold significant value in assessing the controllers, making them a notable advantage of this method. Implementing these indicators straightforwardly or even achieving them at all may pose challenges or be unattainable in other methods. In addition, the method of designing the CDM controller is extremely rational and easy to comprehend. It also has a straightforward structure and straightforward calculations that are not difficult to implement. Because of these characteristics, the CDM controller is a strategy that is accurate, practicable, and dependable in the industry.
Nevertheless, with the salient advantages of CDM controllers, there are challenges, such as designing the key parameters of it, i.e., stability index and equivalent time constant. Adjustment of these two parameters is according to the objectives required for the stable operation of this controller, which has been discussed and researched in many studies, and various ranges have been introduced to determine and adjust them [42]. However, the proposed methods lack a clear process, and it is not determined for what values the best performance is achieved. Thus, in order to surmount these challenges and achieve optimal values, this paper introduces the novel TFWO algorithm, which incorporates a robust objective function for the first time. In essence, the novelty of this paper lies in the introduction and enhancement of the CDM algebra controller's performance by optimally designing its key parameters in accordance with mathematical principles and governing limits. Consequently, a hybrid (algebra-optimal) CDM controller is devised for the AVR system, marking the first instance of its implementation through a novel algorithm. Subsequently, the controller coefficients are calculated for the automatic voltage regulation system. This new algorithm, which is inspired by the whirling flow of water, is proposed to solve the optimization problem. Considering the No Free Lunch (NFL) theory [45], which states that no single algorithm can effectively address all engineering and optimization problems, this paper introduces a novel algorithm to tackle the specific challenges at hand. The proposed algorithm provides advantages such as easy implementation, low parameter adjustment, crossing local minima, fast convergence, high exploration, and exploitation, and searching for finding the optimal solution. Additionally, the proposed objective function aims to design a multi-objective CDM controller by utilizing the weighted coefficient method, where the coefficients are summed accordingly. The functions in question are represented in the form of ITSE criteria, which prioritizes errors with greater magnitudes and longer durations within the system. The aims include minimizing the controller output signal to avoid saturation, reducing costs, achieving faster settling time and the peak time for improved response speed, and increasing the minimum damping ratio (MDR) of the system to enhance the stability and robustness of the designed controller. These functions have become a comprehensive objective function using the sum of weighted coefficients methods.
To show the efficiency of the proposed control strategy when faced with load step changes and uncertainties due to large changes in dynamic values, it is tested on the sample system. Moreover, using the classic PID controller of [8], the desired performance indices in both time and frequency domains are compared. The figures and numerical data exhibit the superiority of the proposed control strategy through various performance criteria, including overshoot, undershoot, peak-to- peak, settling time, ITSE, and the MDR. In general, the main objectives and contributions of the paper can be listed as follows:
• The paper introduces and enhances a combination of the CDM algebra controller with a powerful mathematical back up and optimizing its key parameters according to all mathematical rules and its governing limits and, as a result, designing a hybrid (algebra- optimal) CDM controller for the AVR system for the first time.
• The CDM controller’s key parameters are optimized by employing a novel algorithm incorporating a combined objective function. This objective function aims to minimize the ITSE, the controller output signal, the settling time, and the peak time while simultaneously increasing the MDR.
• It is essential to utilize qualitative and quantitative data in both the time and frequency domains to demonstrate the superiority of the suggested control technique. This is particularly important when addressing load step changes and uncertainties arising from significant variations in dynamic values.
The paper is structured as follows: Section 2 provides an overview of the AVR system modeling, including the description of transfer functions. Section 3 discusses the design of the CDM controller, accompanied by an explanation of the TFWO algorithm and the objective function. In Section 4, the simulation results of the proposed method applied to the AVR system are presented, analyzed, and summarized in two subsections. Finally, the paper concludes with the overall findings and conclusions.
The AVR System Modeling
The AVR loop ensures voltage stability within the power system. The AVR system, which plays a crucial role in the power system, consist of four primary components: an amplifier, an actuator, a generator, and a sensor [8,17,18]. A voltage sensor constantly measures and transmits the terminal electrical potential difference. The voltage waveform undergoes rectification and smoothing within a comparator, where it is compared to a direct current (DC) signal source. Subsequently, the error voltage derived from the comparator output is enhanced by an amplifier. Ultimately, this signal is utilized to regulate the excitation of the generator field winding. Figure 1 illustrates the actual model of the AVR system.
This Figure demonstrates that six components of a basic AVR system, including an amplifier, an exciter, a generator, a sensor, a comparator, and a controller. Based on the information presented in Figure 1, the transfer functions of various components within
the AVR system are outlined below:
The Transfer Function of the Amplifier
The amplifier’s transfer function is represented by Eq. (1), where it is modeled using a gain and a time constant [18].
The parameters KA and τA in the equation represent the gain and time constant of the amplifier system, respectively. The value of KA typically falls within the range of 10 to 40, while the time constant τA varies between 0.02 seconds and 0.1 seconds.
The Transfer Function of the Exciter
The transfer function of the exciter is represented in a similar manner to that of the amplifier, utilizing a gain and a time constant, as illustrated in Equation (2) [18].
The Transfer Function of the Generator
The transfer function for the terminal voltage of the generator is represented by Equation (3) [18].
The parameters KG and τG denote the gain and time constant of the generator model, respectively. The value of KG falls within the range of 0.7 to 1.0, while the time constant τG varies between 1.0 and 2.0.
The Transfer Function of the Sensor Component
The transfer function of the sensor is represented by Equation (4), where it is modeled using an increment and a time constant [18].
The parameters KS and τS represent the gain and time constant of the sensor model, respectively. The value of KS ranges from 0.9 to 1.1, while the time constant τS varies between 0.001 and 0.06. Figure 2 presents the block diagram of the AVR system, depicting the arrangement of components based on Figure 1 and the transfer functions associated with each component.
Design of the AVR System Controller
Coefficient Diagram Method
In 1991, Professor Shunji Manabe introduced the coefficient diagram method (CDM), which is an algebraic approach that utilizes polynomial expressions to mathematically represent a system [46]. Polynomial representation of the controller and plant are used in this method. To achieve this objective, a control system structure with two degrees of freedom (2DOF) is employed, ensuring the absence of any significant overshoots. Furthermore, unlike optimal controllers, CDM leverages a robust mathematical framework to facilitate pole placement and indirectly determine the settling time. Through this, a desirable robust controller is designed and desirable response is obtained. Thus, speed, stability and robustness, which are the three key parameters in controller designing are gained. This can be considered as a major advantage of this method, which is pretty unique. The methodology for the design is flawlessly scientific and effective, and the execution is straightforward. Because of it, the CDM-based controller may now serve industrial purposes with increased precision, viability, and dependability. [46, 47].
In CDM, there is a tool called as "Coefficient Diagram" that is quite helpful and powerful. This tool, along with Bode and Nyquist diagrams, is applied in the process of designing controllers. By examining this particular figure alone, we can obtain valuable insights into the time response speed, stability, and robustness criteria. The convexity level of a curve may be established by analyzing the coefficients of the feature’s polynomial in conjunction with the curve's overarching tendency. The extent to which the ai curve shifts in response to variations in the plant's parameters serves as an indicator of the system's stability, response speed, and resilience. The necessary condition for stability may be precisely calculated by using this diagram in conjunction with the Routh criterion for lower orders and the Lipatoy criteria for higher orders [48]. Figure 3 illustrates the block diagram representation of a single-input, single-output (SISO) system employing the CDM.
The presence of two numerators in the controller's transfer function signifies a two-degree-of- freedom (2DOF) structure. By utilizing a two-degree-of-freedom (2DOF) structure, the focus can be directed toward addressing disturbances and tracking the reference signal. The output of the controller system is expressed as follows:
Whereby, the characteristic polynomial of the closed-loop system is denoted by P(s), and it is defined as follows:
The following gives A(s) and B(s).
For practical reasons, p>=q is an essential condition and by substituting (7) in (6), P(s) is obtained:
Determining the parameters τ and Yi is a critical factor in the design of the CDM controller. The parameter τ affects the magnitude of the control signal and the speed of the system. The stability and shape of the time response are determined by the parameter Yi. The parameters and ai exhibit the following variations:
Based on the standard form of S. Manabe, Yi values can be {2.5, 2, 2 . . . 2} that can lead to desirable performance. Stability indices are determined as Yi=1.5~4 too, which is due to Routh and Lipatov’s criteria of stability. Results have shown that stability is guaranteed and all poles are negative when Yi> 1.5Yi* and all of Yi> =1.5. These standards indicate that to have an acceptable and logical design, τ must be as follows [42]:
By setting P(s) equal to Ptarget(s), the coefficients of the A(s) and B(s) polynomials are determined. In addition, the reference numerators polynomials F(s) are obtained as follows:
TFWO Algorithm
The TFWO algorithm was originally introduced by Ghasemi et al. in their publication [49]. The inspiration behind this optimization approach stemmed from the turbulent flow observed in water. The core of the whirlpool behaves in a manner like to that of a sink or a vacuum by drawing nearby objects and particles into its center and farther into the vortex. This action may be seen as the application of centrifugal force to the particles. This force is ultimately overcome by the centrifugal force. The centripetal and centrifugal forces that were acting upon the particle are shown in Fig. 4 (a). Several stages, including the following, are represented for the TWFO algorithm:
• The influence of whirlpools on the objects and particles that are a member of their set as well as the set of other whirlpools
• The process of establishing the whirlpool (NWh: a collection of whirlpools)
• The force of centrifugal acceleration
The interactions between individual whirlpools
• The beginning of the construction of the whirlpool (NWh: a group of whirlpools)
The algorithm's starting population, denoted by Np, is evenly distributed across the NWh groups, also known as whirlpools. Then, the member of the population of each whirlpool (Wh) with the highest strength is chosen to serve as the center or sink of that whirlpool. This causes the objects and particles (X) to be pulled toward the whirlpool center in proportion to how close they are to the center.
• The impact of whirlpools on the items and particles that are a component of the whirlpool's set as well as those of other things and particles
When an item is sucked up by the whirlpool, its position and that of the whirlpool become the same, which is when the updating vector of particle positions takes effect; this is represented by the equation Xi = Whj. Other whirlpools, on the other hand, may deviate items from their location and absorb them dependent on where they are and how much suction strength they have, which is given by the objective value (f(Whj)). The value demonstrates the extent of this discrepancy. Therefore, the jth item, which was located at Xi, moves as a result of the centripetal force exerted by the whirlpool Whj, and the displacement of the object as a result of the other whirlpools is ∆Xi . The parameter that represents the rotation angle of the particle in the updating vector is denoted by the letter, and its value is modified after each iteration. The procedure for upgrading is shown in Fig. 4 (b).
• Centrifugal force
When things move into a whirlpool under the influence of a centrifugal force, another force that is also called centrifugal force (FE) is applied to the item, and it causes the object to move away from the vortex. When this happens, the item moves to a new location as a result of the centrifugal force, which is larger than both the tension and the centrifugal force. Calculations of centrifugal force and the impact of centrifugal force may be found by using the following equations:
• The whirlpools' interactions with one another whirlpools
The whirlpools interact with one another and produce movement in both of themselves, in addition to the impact that the whirlpool has on the items. This movement is analogous to the movement of items toward a whirlpool, and any vortex that has a more powerful centrifugal force will move the whirlpool around it and swallow it up. Following are some formulae that may be used to compute the displacement of nearby whirlpools in relation to one another:
Defining the Optimization Problem and Objective Function
Obtaining key parameters is an essential step in the process of constructing a CDM controller, as was previously indicated. In the earlier references, the selection of these parameters is accomplished via trial and error; there is no particular mathematical technique involved. In addition, it is not quite obvious if the key parameters lead to the best feasible outcomes. Therefore, to solve these problems, this paper attempts to apply an optimal- algebraic CDM controller for the AVR system for the first time. The smart combination of algebraic CDM and optimization methods considering all of its mathematical rules is used in the proposed controller. Therefore, to design a powerful controller with fast response and maximum stability, an optimization problem is defined and four objective functions are considered as follows.
• The ITSE index for voltage variations
There are several indices in the design of controllers, including ITAE, IAE, ITSE, and ISE, each of which has advantages. However, the ITSE index takes precedence as the primary objective function due to its incorporation of the advantages of other indices while also ensuring a rapid dynamic response. This objective function for the AVR system is defined as follows:
• Settling time and peak time
To increase the response speed and reduce its settling time, as well as to reduce the amplitude and peak time, the second objective function is defined as follows:
Control cost
By paying any attention to f2 and f1 of voltage fluctuations, the response may be made to move at a quicker rate; however, this may result in an increase in control gain. As a consequence of this, raising the control gain is seen as a flaw in terms of controller design. In simpler terms, having a lower control gain brings advantages such as prevention of actuator saturation, reduction in the cost of monitoring a larger actuator, and diminishment of the output signal (u). In light of this, the third objective function
• Minimum damping ration (MDR)
To achieve a more stable response, an objective function is employed, which focuses on maximizing the MDR of all eigenvalues. This objective function is referred to as the fourth objective function and is given in the following equation:
Given that there are four objective functions, it is necessary to employ a method that can minimize all of these functions equally and within a single range to solve the optimization problem.
To this end, the sum of the weighted coefficients method for objective functions has been converted into a single objective function. Finally, the general objective function is considered as follows using the sum of weighted coefficients method:
Where ωis are weighted coefficients, the sum of which is equal to one. The αi coefficients are utilized to ensure equal weighting of each term and promote competitiveness among them throughout the optimization process. The optimization problem is defined in this paper as follows:
Applying the TFWO Algorithm to the Optimal CDM Controller
This section describes how to connect and design a hybrid CDM controller and TFWO algorithm. The connection block diagram of the proposed controller to the AVR system is depicted in Figure 5. Moreover, the algorithm flowchart, along with the calculation of the parameters and objective functions is shown in Figure 6.
Simulation Results
The System Under Study
In this section, the simulation outcomes of implementing the proposed method for AVR control in the generator excitation system are presented, aiming to minimize voltage fluctuations. To this end, the optimized CDM control strategy optimized by the TFWO is applied to the standard voltage control sample model of Figure 2 and is compared with the classic PID controller in Table 1 [8]. The parameters of the system being analyzed, along with the AVR system within the defined range, are presented in Table 2. Information about the algorithm is also given in the Appendix section of the paper.
Simulation of the CDM Controller
To adjust the two key parameters of CDM, an optimization method with a new algorithm and a powerful objective function is proposed. Also, a second-order CDM controller (2/2) is used to control the voltage of the test system.
To optimize the parameters Yi and τ, the transfer function is first linearized and the AVR open loop is extracted in a decentralized way. Then, a combination of CDM algebraic strategy and optimization is performed according to all the mathematical rules and calculations and governing limits mentioned in the previous section. The optimized parameters are defined within the upper and lower limits as specified in Table 3. After running the algorithm several times and finding the best optimized parameters, the final coefficients related to the forward polynomials and the CDM controller feedback according to the relevant equations in the previous section and the least- squares method is obtained to solve the set of over-determined equations due to degree reduction.
Figure 7 shows the convergence of the TFWO algorithm and Table 4 lists the optimized final responses. CDM algebraic calculations are also given below. As can be seen, all the relationships governing the CDM control structure are observed and the settling times are optimized in proportion to the equivalent time constant.
Figure 8 presents the coefficient diagram, where the horizontal axis represents the order "i" values associated with each coefficient. The related description is provided in the previous sections.
Numerical and simulation results in the time and frequency domains obtained by comparing the reference control and the optimal CDM controller strategies proposed in the system under study are shown in Figure 9 and Table 5. According to the graph and especially the numerical results based on sitting time, peak time, and ITSE in less time and higher MDR as a result of the proposed control strategy, it is obvious that optimal CDM offers better performance than the reference classic PID.
Robustness of the CDM Controller
A sensitivity analysis was carried out to assess the resilience of the proposed optimized CDM control strategy when confronted with variations in the range of dynamic parameters. A comparison was conducted between the two control strategies under the condition of significant variations in all dynamic parameters, ranging from ± 50%. Numerical results based on the MDR are listed in Table 6 and the step response of AVR is shown in Figure 10. According to the eigenvalue studies, it is obvious that the responses obtained from the optimal CDM control strategies are more stable and robust than the compared PID control strategy due to the higher value of MDR when dealing with uncertainties. It is noteworthy that under the most severe uncertainties studied, the optimal MDM control strategy maintains the stability of the voltage control system under study in terms of positive MDR, while the PID controller has unstable modes with a positive true part and as a result a negative MDR.
The remaining sensitivity analysis investigations were conducted by introducing a maximum uncertainty of 50% in all time constants pertaining to the proposed control strategy. Figure 11 illustrates the diagrams and root loci under the specified conditions. The observed insensitivity in this study signifies the robustness of the system, as it maintains consistent dynamic responses even in the face of significant uncertainty. Consequently, once the optimized parameters of the proposed control strategy are acquired at the operating point, there will be no further need for readjustment. The results of the sensitivity analysis align with the designer's expectations regarding the optimization of key parameters in the CDM controller, highlighting the proposed control strategy's speed, stability, and robustness.
Moreover, to indicate the correct performance of the optimized CDM controller against different step changes in reference voltage, the response of the AVR system with the proposed controller is shown in Figure 12. According to the simulation results, the CDM controller provides a fast and stable performance and also proving the robust performance of the suggested controller against unforeseen changes.
Conclusion
Since the AVR system in voltage control of the generator and stability of power system are of high importance, the proposed method in this paper was studied for the better and more stable control of the AVR system and power system. In this study, a novel approach was employed for the first time, utilizing a combination of an algebraic CDM controller and optimization its key parameters, to regulate the voltage of the generator excitation system. The initial step in optimizing the critical parameters of CDM involved extracting the open-loop transfer function of AVR. Next, the TFWO algorithm was used to perform a combination of algebraic CDM strategy and optimization in accordance with all mathematical rules, calculations, and governing limits. Finally, the CDM critical parameters were optimized. For the optimized parameters, the upper and lower limits were considered reasonable according to the problem formulation. The final coefficients related to the forward and feedback polynomials of the CDM controller were obtained according to the relevant governing equations and the least-squares method to solve the system of over-determined equations due to degree reduction. In this approach, the TFWO algorithm is employed for optimization, which serves as a comprehensive and potent objective function. The primary focus is on reducing the ITSE criteria over time, enhancing the performance of the controller's output signal, minimizing settling time and peak time, and improving the MDR. The control strategy's effectiveness was demonstrated by conducting simulations on a standard system. The visual and numerical results of generator terminal voltage were obtained for overshoot, undershoot, peak to peak, settling time, peak time, ITSE, and MDR criteria. Responses obtained by the proposed optimal CDM control strategy are faster, more stable, and more robust than those of the reference classic PID controller. Concerning the sensitivity analysis, the optimized parameters of the suggested control strategy, obtained once at the operating point, do not need any additional modifications. Based on the several visual and numerical results in frequency and time domain, this is an accurate, feasible, and reliable strategy to be realized in the industry.
Appendix
Parameters of the AVR System
KA = 10; TA = 0.1; KE = 1.0; TE = 0.4; KG = 1.0; TG = 1.0; KS = 1.0; TS = 0.05;
Parameters of the TFWO Algorithm
Max Iterations = 100, Number of search agents = 40
- Organization WH. Coronavirus. WHO (2020) https://doi.org/ https://www.who.int/health- topics/coronavirus#tab=tab_1.
- Buonaguro L, Tagliamonte M, Tornesello ML, Buonaguro FM (2020) SARS-CoV-2 RNA polymerase as target for antiviral therapy. J Transl Med 18:185.
- Ruiz Estrada MA, Park D, Lee M (2020) The Evaluation of the Final Impact of Wuhan COVID-19 on Trade, Tourism, Transport, and Electricity Consumption of China. SSRN Electron J.
- Implications of COVID-19 for the electricity industry: A comprehensive review. CSEE J Power Energy Syst 2020.
- Tsao YC, Thanh VV, Lu JC, Wei HH (2021) A risk-sharingbased resilient renewable energy supply network model under the COVID-19 pandemic. Sustain Prod Consum 25: 484-98.
- Santiago I, Moreno-Munoz A, Quintero-Jiménez P, Garcia-Torres F, Gonzalez-Redondo MJ (2021) Electricity demand during pandemic times: The case of the COVID-19 in Spain. Energy Policy 148: 111964.
- Werth A, Gravino P, Prevedello G (2021) Impact analysis of COVID-19 responses on energy grid dynamics in Europe. Appl Energy 281: 116045.
- Saadat H (1999) Power system analysis. vol. 2. McGraw-hill.
- Belwin Edward J, Rajasekar N, Sathiyasekar K, Senthilnathan N, Sarjila R (2013) An enhanced bacterial foraging algorithm approach for optimal power flow problem including FACTS devices considering system loadability. ISA Trans 52: 622–8.
- Hingorani NG, Gyugyi L (2000) Understanding FACTS: Concepts and Technology of Flexible AC Transmission Systems. Wiley
- Kundur P, Balu NJ, Lauby MG (1994) Power system stability and control. McGraw-Hill.
- Padiyar KR (2004) Power System Dynamics: Stability and Control. Anshan.
- Gaing ZL (2004) A Particle Swarm Optimization Approach for Optimum Design of PID Controller in AVR System. IEEE Trans Energy Convers 19: 384-91.
- Pan I, Das S (2013) Frequency domain design of fractional order PID controller for AVR system using chaotic multi- objective optimization. Int J Electr Power Energy Syst 51: 106-18.
- Aghaie Z, Amirifar R (2008) An LMI Approach to Robust Controller Design for AVR System. 2008 40th Southeast. Symp. Syst. Theory, IEEE 17-24.
- Das S, Pan I ()2014 On the Mixed <inline-formula><- tex-math notation="TeX">${{\rm H}_2}/{{\ rm H}_\infty }$</tex-math></inline-formula> Loop-Shaping Tradeoffs in Fractional- Order Control of the AVR System. IEEE Trans Ind Informatics 10: 1982–91.
- Modabbernia M, Alizadeh B, Sahab A, Moghaddam MM (2020) Robust control of automatic voltage regulator (AVR) with real structured parametric uncertainties based on H∞ and μ-analysis. ISA Trans 100: 46-62.
- Gozde H (2020) Robust 2DOF state-feedback PI-controller based on meta-heuristic optimization for automatic voltage regulation system. ISA Trans 98: 26–36.
- Kumar A, Kumar V (2017) A novel interval type-2 fractional order fuzzy PID controller: Design, performance evaluation, and its optimal time domain tuning. ISA Trans 68: 251–75.
- Al Gizi AJH, Mustafa MW, Al-geelani NA, Alsaedi MA (2015) Sugeno fuzzy PID tuning, by genetic-neutral for AVR in electrical power generation. Appl Soft Comput 28: 226–36
- Aguila-Camacho N, Duarte-Mermoud MA (2013) Fractional adaptive control for an automatic voltage regulator. ISA Trans 52: 807–15.
- Pan I, Das S, Gupta A (2011) Tuning of an optimal fuzzy PID controller with stochastic algorithms for networked control systems with random time delay. ISA Trans 50: 28–36.
- Batmani Y, Golpîra H (2019) Automatic voltage regulator design using a modified adaptive optimal approach. Int J Electr Power Energy Syst 104: 349–57.
- J.h. Al Gizi A, Mustafa MW, M.a. Al Zaidi K, K.j. Al-Zaidi M (2015) Integrated PLC-fuzzy PID Simulink implemented AVR system. Int J Electr Power Energy Syst.
- Shayeghi H, Younesi A, Hashemi Y (2015) Optimal design of a robust discrete parallel FP + FI + FD controller for the Automatic Voltage Regulator system. Int J Electr Power Energy Syst 67: 66–75.
- Pan I, Das S (2012) Chaotic multi-objective optimization based design of fractional order PIλDμ controller in AVR system. Int J Electr Power Energy Syst 43: 393–407.
- Modabbernia M, Alizadeh B, Sahab A (2020) Mirhosseini Moghaddam M. Designing the Robust Fuzzy PI and Fuzzy Type2 PI Controllers by Metaheuristic Optimizing Algorithms for AVR System. IETE J Res 1–15.
- Chatterjee S, Mukherjee V (2016) PID controller for automatic voltage regulator using teaching–learning based optimization technique. Int J Electr Power Energy Syst 77: 418–29.
- Nahas N, Abouheaf M, Sharaf A, Gueaieb W (2019) A Self-Adjusting Adaptive AVR-LFC Scheme for Synchronous Generators. IEEE Trans Power Syst 34: 5073–5.
- Mukherjee V, Ghoshal SP (2007) Intelligent particle swarm optimized fuzzy PID controller for AVR system. Electr Power Syst Res 77: 1689–98.
- Kim DH (2011) Hybrid GA–BF based intelligent PID controller tuning for AVR system. Appl Soft Comput 11: 11–22.
- Micev M, Ćalasan M, Ali ZM, Hasanien HM, Abdel Aleem SHE (2020) Optimal design of automatic voltage regulation controller using hybrid simulated annealing – Manta ray foraging optimization algorithm. Ain Shams Eng J.
- Jumani TA, Mustafa MW, Hussain Z, Md. Rasid M, Saeed MS, Memon MM, et al. (2020) Jaya optimization algorithm for transient response and stability enhancement of a fractional-order PID based automatic voltage regulator system. Alexandria Eng J 59: 2429-40.
- Sikander A, Thakur P, Bansal RC, Rajasekar S (2018) A novel technique to design cuckoo search based FOPID controller for AVR in power systems. Comput Electr Eng 70: 261–74.
- Çelik E, Durgut R (2018) Performance enhancement of automatic voltage regulator by modified cost function and symbiotic organisms search algorithm. Eng Sci Technol an Int J 21:1104–11.
- Mokeddem D, Mirjalili S (2020) Improved Whale Optimization Algorithm applied to design PID plus second-order derivative controller for automatic voltage regulator system. J Chinese Inst Eng 43: 541–52.
- Kose E (2020) Optimal Control of AVR System With Tree Seed Algorithm-Based PID Controller. IEEE Access 8: 89457–67. 38. Sahib MA (2015) A novel optimal PID plus second order derivative controller for AVR system. Eng Sci Technol an Int J 18: 194–206.
- Niknam T, Azizipanah-Abarghooee R, Rasoul Narimani M (2012) A new multi objective optimization approach based on TLBO for location of automatic voltage regulators in distribution systems. Eng Appl Artif Intell 25: 1577–88.
- Bernard MZ, Mohamed TH, Mitani Y, Qudaih YS (2013) CDM application on power system as a load frequency controller. 2013 IEEE Electr. Power Energy Conf., IEEE; 1–5.
- Bernard MZ, Mohamed TH, Qudaih YS, Mitani Y (2014) Decentralized load frequency control in an interconnected power system using Coefficient Diagram Method. Int J Electr Power Energy Syst 63: 165–72.
- Heshmati M, Noroozian R, Jalilzadeh S, Shayeghi H (2020) Optimal design of CDM controller to frequency control of a realistic power system equipped with storage devices using grasshopper optimization algorithm. ISA Trans 97: 202–15.
- Mohamed TH, Shabib G, Ali H (2016) Distributed load frequency control in an interconnected power system using ecological technique and coefficient diagram method. Int J Electr Power Energy Syst 82: 496–507.
- Ali R, Mohamed TH, Qudaih YS, Mitani Y (2014) A new load frequency control approach in an isolated small power systems using coefficient diagram method. Int J Electr Power Energy Syst 56:110-6.
- Wolpert DH, Macready WG (1997) No free lunch theorems for optimization. IEEE Trans Evol Comput 1: 67-82.
- Manabe S (1998) Coefficient Diagram Method. IFAC Proc Vol 31: 211-22.
- Manabe S (2003) Importance of coefficient diagram in polynomial method. 42nd IEEE Int. Conf. Decis. Control (IEEE Cat. No.03CH37475), IEEE; n.d., p. 3489-94.
- Manabe S (2005) Case studies of coefficieant diagram method–practical polynomial design approaches. IFAC Proc Vol 38: 904-9.
- Ghasemi M, Davoudkhani IF, Akbari E, Rahimnejad A, Ghavidel S, Li L (2020) A novel and effective optimization algorithm for global optimization and its engineering applications: Turbulent Flow of Water-based Optimization (TFWO). Eng Appl Artif Intell 92.